No. SS2-AVP302-0100 (Rev.14) Azbil Corporation
- 2 -
FUNCTIONAL SPECIFICATIONS
Applicable actuator
• Single and double acting actuator
• Linear and rotary motion actuator
Approvals
TIIS Flameproof approval
Ex d IIC T6 Certificate No.TC16388
KOSHA Flameproof approval
Ex d IIC T6
FM Explosionproof approval
Explosionproof
for Class I, Division 1, Group A, B, C, D
Dust-ignition for Class II, Division 1, Group E, F, G
Suitable for Class III, Division 1
Flameproof for Class I, Zone 1, AEx d IIC T6 at
Ambient temperature < 80°C
Installation should comply with NEC.
FM Intrinsically safe approval
Intrinsically safe for Class I, II, III, Division 1,
Group A, B, C, D, E, F, G, T4
Intrinsically safe for Class I, Zone 0, AEx ia IIC T4
Nonincendive for Class I, Division 2, Group A, B,
C, D, T5
Suitable for Class II, III, Division 2, Group F, G, T4
The barriers should be FM recognized types and
comply with the following conditions as follows.
Input signal line: 12.02 ≤ Vmax ≤ 30 V,
Imax = 100mA, Pmax = 1 W, Ci = 0
μF
, Li = 0.22 mH
Installation should comply with NEC.
CSA Explosionproof approval
Explosionproof for Class I, Division 1, Group B, C,
and D
Flameproof for Class I, zone 1, Ex d IIC, T6
Dust ignition proof for Class II and III Division 1,
Group E, F and G Type 4X,
Certificate No. 188352-1028066 (LR113752-6)
ISSeP/ATEX Flameproof approval
II 2 G EEx d IIC T6 at -20°C < T
amb
< +70°C
IEC IP66 Certificate No. ISSeP 02ATEX056
KEMA/ATEX Intrinsically safe approval
II 1 G Ex ia IIC T4
II 1 D Ex iaD 20 IP66 T135°C
Certificate No. KEMA 00ATEX1111 X
IEC IP66
The barriers should be ATEX certified types and comply
with the following condition as follows.
Input circuit (terminals ±IIN)
Ui = 30 V, Ii = 100mA (resistively limited),
Pi = 1 W, Ci = 26 nF, Li = 0.2 mH
Both circuits shall be considered to be connected to
ground from a safety point of view.
NEPSI Flameproof approval
Ex d IIC T6, with NEPSI Dust ignition DIP A20 Ta T6
IP66
Flameproof cable gland which is NEPSI Ex d II C T6
recognized is recommended.
NEPSI Intrinsically safe approval
Ex ia IIC T4-T6
The barriers should be NEPSI certified types and comply
with the following condition as follows.
Input circuit (terminals ±IIN)
Ui = 30 V, Ii = 95 mA
Pi = 0.66 W, Ci = 0 μF
Li = 0.2 mH
Output circuit (terminals ±IOUT)
Ui = 30 V, Ii = 95 mA
Pi = 0.66 W, Ci = 0 μF
Li = 0.2 mH
Combination of NEPSI Flameproof and
Intrinsically safe
When used as NEPSI Flameproof, it complies NEPSI
Flameproof approval as above,
When used as NEPSI Intrinsically safe, it complies
NEPSI Intrinsically safe approval as above.
Control signal input
4-20 mA DC (Configurable to any required range for
split range.)
Minimum driving current: 3.85mA
Minimum 12.0 Volts available at the positioner
Input resistance
400 Ω typically / 20 mA DC (General, Flameproof and
explosionproof model)
600 Ω typically / 20 mA DC (Intrinsically safe model)
Output characteristics
• Linear, Equal percentage, Quick opening
• Custom user characteristics (16 points)
Stem travel range
Feedback Lever Angle ± 4° to ± 20°
Bypass operation
Auto/Manual external switch (For single acting actuator only)
Air supply pressure
140 to 700 kPa {1.4 to 7.0 kgf/cm²}
Air consumption
4 l/min(N) maximum at 140 kPa {1.4 kgf/cm²}
5 l/min(N) maximum at 280 kPa {2.8 kgf/cm²}
6 l/min(N) maximum at 500 kPa {5.0 kgf/cm²)}
10 l/min(N) maximum at 400 kPa {4.0 kgf/cm²}
for double acting actuator
Maximum air deliver flowrate
110 l/min(N) at 140 kPa {1.4 kgf/cm²}
250 l/min(N) at 400 kPa
{
4.0 kgf/cm
²}
for double acting actuator
Output balanced pressure
55 ± 5% for double acting actuator only
Lightning protection
Peak value of voltage surge: 12 kV
Peak value of current surge: 1000 A